Rating Voltage/Frequency | 200Kw at 400VAC, 3 phase 4 wire, 50 Hz, |
Max Load Power | Resistive load:200kW |
Load Steps | 1kW,2kW,2kW,5kW,10kW,20kW,20kW,50kW, 100kW,min load step: 1 kW |
PF(Power Factor) | 1 |
Load Accuracy (each step) | ±5% |
Load Accuracy (overall) | 3% |
Display Precision | 0.5 grade |
Control Power | 220VAC, 1 phase 50 Hz, |
Wire Connection | Load power supply input——busbar Control power supply input——three pin socket |
Insulation | F |
Way of Working | Continuous Work |
Cooling | Fan forced cooling, horizontal inlet air and vertical outlet cooling |
Casing Color | Grey(RAL7035) |
Dimensions | 1450 mm*900mm*870mm(length*wide*high) |
Weight | About 750kgs |
Temperature | -10℃~+50℃ |
Relative Humidity | ≤95% |
Altitude | ≤1500 meter |
Contactor | Schneider |
Fuse | DELIXI |
Alloy Resistance | (self-developed) |
Product Advantage
Stable Running: with the latest generation control module as the core, a sharp rise in system response speed and anti-interference performance, avoid function failure in complex electrical environment, and ensure system running stably and reliably.
Application
KX Load Banks can be used to satisfy the requirements for emergency stand-by power systems. These requirements concern acceptance testing and periodic on-site testing and maintenance of emergency and stand-by power systems. The essence of the requirements is that emergency and stand-by power systems are to be tested under load.