Brand Name :KAIXIANG
Model Number :100KW
Certification :ISO9001
Place of Origin :HEBEI CHINA
MOQ :ONE SET
Price :negotiable
Payment Terms :L/C, D/A, D/P, D/P, T/T, Western Union, MoneyGram, D/P
Supply Ability :20 SETS ONE MONTH
Delivery Time :ONE MONTH AFTER GET DEPOSIT
Packaging Details :WOODEN CASE
Rating Voltage :400VAC/50Hz, 3 phase 4 wir
Rated Load Power :Resistive load: 100kW
Rated Voltage :400 VAC
Installed Capacity :Resistive load: 100kW
Load Tolerance(overall) :±3%
Control Power :220VAC/50Hz,single phase
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

Long Life Quick Charge 100kw Generator Dummy Load Testing

Product Description


1.our load bank an accurately test output power and load capacity with all kinds of generators.
2.System consists of testing/control and load bank, mainly includes AC load bank, data capture system, auto load/unload control system, heat dissipation device, assist control and PC software.
3.User can control load bank through local control panel, also through software

Technical Parameters

Rating Voltage/Frequency 400VAC/50Hz, 3 phase 4 wire,
Rated Load Power Resistive load: 100kW
Installed Capacity Resistive load: 100kW
Load Step 1,2,2,5,10,10,20,50kW, min step load: 1kW
PF(Power Factor) 1
Load Tolerance (each step) ±5%
Load Tolerance(overall) ±3%
Display Precision 0.5 class
Control Power 220VAC/50Hz, single phase
Wire Connection

Load power supply input——terminal block
Control power supply input——three pin socket

Insulation F
Duty Cycle Continuous
Casing Dimensions and Cooling about 860*570*710mm (length*width*height) Forced air cooling,Horizontal inlet air,Horizontal outlet air
Weight About 120kgs/set
Transportation Hoisting, there are lifting lug in top of casing
Casing Color Grey(RAL7035)
Ambient Temperature -10℃~+50℃
Relative Humidity ≤95%
Altitude ≤1500 meter
Atmospheric Pressure 86~106kPa
Contactor Schneider
Fuse DELIXI
MCU INFINEON
Data processing software Kaixiang(self-developed)
Alloy Resistance Kaixiang(self-developed)


Product Advantage

System can load power in rated range, measure generator steady-state 3 phase voltage, current, active power, power factor, frequency, and running time, and simulate the generator set, UPS real load working state. Power input using sectional type, energy dissipation type load, forced-air cooling, 3 phase fan decentralized supply air, air-flow is sufficient and low noise.

Application

Large generator system testing in ocean engineering, drilling facilities,ship construction
etc field
Factory testing for generator, static voltage characteristic test, speed characteristic test;
Marine generator overload protection test,parallel operation test,reverse power and reverse current protection test
Assist shipyard in mooring test,sea trial test