Hebei Kaixiang Electrical Technology Co., Ltd

Manufacturer from China
Active Member
7 Years
Home / Products / AC Load Bank /

Resistive 400v 1500kw Load Bank 3 Phase AC Variable For Generator Testing

Contact Now
Hebei Kaixiang Electrical Technology Co., Ltd
City:shijiazhuang
Province/State:hebei
Country/Region:china
Contact Now

Resistive 400v 1500kw Load Bank 3 Phase AC Variable For Generator Testing

Ask Latest Price
Video Channel
Brand Name :Triumph Load
Model Number :AC400V-1500KW
Certification :ISO9001
Place of Origin :HEBEI CHINA
MOQ :ONE SET
Price :negotiable
Payment Terms :L/C, D/A, D/P, D/P, T/T, Western Union, MoneyGram
Supply Ability :20 SETS ONE MONTH
Delivery Time :ONE MONTH AFTER GET DEPOSIT
Packaging Details :WOODEN CASE
Frequency :50 / 60 HZ
Rated Power :1500 KW
Rated Voltage :400 VAC
Rated Current :Depend
Cooling :Forced air cooling
CasingColor :Grey (RAL7035) or as request
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

Resistive 400v 1500kw Load Bank 3 Phase AC Variable For Generator Testing

Product Description

According to the special requirements of users on site, in the agreement the technical standards Intelligent Load Bank (hereinafter referred to as "system") and its accessories are proposed including their function, performance, usage, structure, installation and test to provide users with a high efficient and reliable choice, in order to meet the need for generator load test.


Technical Parameters

Rating Voltage/Frequency 400VAC 50Hz/60Hz,3phase 4 wire
Max Load Power Resistive Load: 1500kW
Load Step

Resistive Load:16 steps
1,2,2,5,10,10,20,50,100,100,200,200,200,200,200,200kW

Power Factor 1
Load Tolerance(each step) ±5%
Load Tolerance(overall) ±3%
Display Precision 0.5 class
Control Power Supply External 415VAC, 3phase 4wire 50Hz
Wire Connection

Load Power Supply Input——Copper bar (star connection)
Control power supply input——Connector bar

Communication Interface RS232 and RS485
Insulation Class F
Duty Cycle Continuous
Cooling Forced air cooling, horizontal air inlet and air outlet
Transportation Hoisting, there are lifting lug in top of case and wheel castors on the bottom
Chassis color Gray(RAL7035)
Size

Approximately 1900mm*2900mm*2100mm
(Width *Length *Height)

Weight Approximately 2000kg
Ambient Temperature -10℃~+50℃
Relative Humidity ≤95%
Altitude ≤2500meters
Atmospheric Pressure 86~106kPa


Product Advantage

1.High Efficiency Data Management: display real-time testing data, generate form, curve graph or report automatically, also can put data into storage. According to generator set No. set up testing file, support to query at any time, and improve data management efficiency.

2.Comprehensive Protection Function: multiple protection, like over temperature, smoke. When in danger, automatically terminate the test and give alarm to protect safety of personnel and equipment


Application

1.Manufacturers of standby power generators commonly use load banks to test and tune newly assembled units

2.generator has been set up in a test cell within the factory, a test engineer uses the load bank to apply a discrete, selectable electrical load to the generator and measure the response stability and endurance.

3.During this process, the test engineer calibrates and adjusts the generator performance to ensure it meets the intended product specifications and tolerances.

Resistive 400v 1500kw Load Bank 3 Phase AC Variable  For Generator Testing


Inquiry Cart 0