For Diesel Generator 380V 1000KW AC Load Bank For Generator Testing
Product Description
The system consists of 1 sets of 1000 kw load bank. The system is made up of two parts of measurement and control and load, mainly including the dry type ac load, automatic data acquisition system, automatically loading and unloading control system, the cooling device, auxiliary control, remote control box and PC software and so on.
Technical Parameters
Rating Voltage/Frequency | 380VAC/50Hz, 3 phase 4 wire, line voltage 380V, phase voltage 220V |
Rated Load Power | Resistive load: 1000kW |
Installed Capacity | Resistive load: 1010kW |
Load Step | 1,2,2,5,10,20,20,50,100,200,200,200,200kW, min step load: 1kW |
PF(Power Factor) | 1 |
Load Tolerance (each step) | ±5% |
Load Tolerance(overall) | ±3% |
Display Precision | 0.5 class |
Control Power | 400VAC/50Hz, 3 phase 4 wire, 230V 1-phase |
Wire Connection |
Load power supply input——Copper bar (star coupling) Control power supply input——Connector-bar |
Insulation | F |
Duty Cycle | Continuous |
Casing Dimensions and Cooling | about 1600*2400*2100mm (length*width*height) Forced air cooling,Horizontal inlet air,Horizontal outlet air |
Weight | About 1500kgs/set |
Transportation | Hoisting, there are lifting lug in top of casing |
Casing Color | Grey(RAL7035) |
Ambient Temperature | -10℃~+50℃ |
Relative Humidity | ≤95% |
Altitude | ≤2500 meter |
Atmospheric Pressure | 86~106kPa |
Contactor | Schneider |
Fuse | DELIXI |
MCU | INFINEON |
Data processing software | Kaixiang(self-developed) |
Alloy Resistance | Kaixiang(self-developed) |
Product Advantage
1. Stable Running: with the latest generation control module as the core, a sharp rise in system response speed and anti-interference performance, avoid function failure in complex electrical environment, and ensure system running stably and reliably.
2. New Load Bank Technology: using the international advanced AC load bank technology, overcome the old water bank defects, such as bear bumpy, unable to use when go to sea, realize Mooring Trial and Sea Trail, and simulate the real working condition of generator running.
3. Mature Manufacturing Technology: load element using excellent anti-corrosion materials, waterproof insulation container packaging, suitable for adverse environment such as ocean. Internal layout is reasonable, air channel is clear, rapid heat emission, and satisfy continuous working need.
Application
Load Banks are used with Engine Generators, Battery Systems, UPS Systems, Inverters, Ground Power Units, Auxiliary Power Units, Aircraft Power Generators, Wind Generators, and Hydro Generators.