Intelligent/Full Automatic 10.5KV 3000kW Medium Voltage Load Bank
Product Description
The ability to test critical power systems at voltages of 1.2KV to 80kV using direct-connect,
High Voltage Load Bank offers engineers flexibility, time savings, cost savings, space savings and simplicity. It mainly used to commission utility, oil & gas, and industrial power systems without the need for additional transformers and cabling.
Technical Parameters
Rating voltage/frequency | 10.5kV, 3 phase 50Hz |
Max Load Power | Resistive Load: 3000kW |
Load Resolution | Resistive Load: 6steps, 100kW,200kW,300kW,700kW,800kW,900kW |
Power Factor | 1 |
Load Tolerance | ±5% |
Load Tolerance (overall) | ±3% |
Fan &Control Voltage | External AC 3 phase 4 line, 380V/50Hz |
Wire Connection |
Load bank input——Copper bar (star coupling ”Y”) |
Communication Interface | RS485,RS232 |
Insulation | F |
Max Protection Grade | IP54 |
Duty Cycle | Continuous |
Cooling | Forced air cooling, by Axial Fan; horizontal inlet air, vertical exhaust cooling |
Enclosure | Container type,with a ladder, air inlet and outlet with mesh enclosure and protection door |
Internal Lighting | Adequate internal lighting will be provided |
Transportation | Hoisting, there are lifting lug in top of casing |
Color | Grey RAL7035 or as required |
Dimensions | About 6058mm*2438mm*2591mm(L*W*H) |
Ambient Temperature | -10℃~+50℃ |
Relative Humidity | ≤95% |
Atmospheric Pressure | 86~106kPa |
Contactor | Xiguang |
Fuse | Chuantai |
Alloy Resistor | (self-developing) |
Data Processing Software | (self-developing) |
Technology Advantages
1. Standard Testing Function: The load bank can do stable test, transient test, and realize functions, such as setting, fluctuation, instant load, and instant unload.
2. Super Power Load: high load power density, large capacity of single set, parallel running to finish super power testing, and realize tens of megawatts of power loading.
3. Accurate Data: with high precision data collection module and measuring meter, related equipment has passed the certification by CMA (China Metrology Accreditation) qualification testing institution, and ensure the reliability of data.
Application
1. Large generator system testing in ocean engineering, drilling facilities,ship construction etc field
2. Factory testing for generator, static voltage characteristic test, speed characteristic test;
Marine generator overload protection test,parallel operation test,reverse power and reverse current protection test
3. Assist shipyard in mooring test,sea trial test
4. Assist with the acceptance of the vessel generator test