415V 300kW Portable Load Bank In Automaticlly and Grey Black Colour
Introduction
1, AC415V-300kW Portable Load Bank In Automaticlly combine the dry type load module with automatic measurement and control module, it can accurately test output power and load capacity of all kinds of generators, offer scientific and high efficiency testing method for large power generator set.
2, It is composed of measurement & control part and load part, mainly including dry type AC load bank, data acquisition system, auto load/unload control system, cooling system, auxiliary control etc.
Applications
emergency stop: you can press the Emergency Stop switch in the panel, when the load bank is locked in this state, it cannot add any load.
overvoltage protection: when input voltage is over the safe value, it can unload automatically and give an alarm.
short circuit protection: when short circuit, fuses in the load bank can insure to unload automatically.
overheating protection: when temperature is over the safe value, it can unload automatically and give an alarm.
fan interlock protection: load bank cannot add any load when working power of fan is off.
Technical specification
Technical Parameters | |
Rating Voltage/Frequency | AC 415V/50Hz, 3 phase 4 wire |
Max Load Power | Resistive Load:300kW |
Load Step | Resistive Load:10 steps; 1,2,2,5,10,20,20,50,100,100kW |
Power Factor | 1 |
Load Tolerance(each step) | ±5% |
Load Tolerance(overall) | ±3% |
Control Power Supply | Input415VAC 3 phase 50Hz |
Wire Connection |
Load Power Supply Input——Copper bar (star connection) Control power supply input——connector bar |
Communication Interface | RS485, RS232 |
Insulation Class | F |
Working Mode | Continuous Working |
Cooling | Forced air cooling,Horizontal inlet air,Horizontal outlet |
Transportation | Hoisting, there are lifting lug in top of case and wheel castors in bottom |
Chassis color | Grey (RAL7035) |
Dimension | About1460mm*1980 mm*1800mm(L*W*H) |
Weight | Approximately 500kg |
Operating Environment Parameter | |
Ambient Temperature | -10℃~+50℃ |
Relative Humidity | ≤95% |
Altitude | ≤2500 meters |
Atmospheric Pressure | 86~106kPa |
Main features
Control Pattern interlock, there is control pattern switch, when choose one control pattern, operation of other pattern is invalid, avoid the clash.
Local meter display data: local meter can display 3 phases voltage, current, active power, frequency and so on.
Load testing: load power that not beyond the rated power, testing and display stable state 3 phases voltage, current, active power, frequency, working time, etc of generator sets.
Load/unload with one key: Whether manual control, remote control or software control, user can preset the power, then press load master button. Load bank loaded according to preset power to avoid load fluctuation during the power changing.
Control Pattern: user can choose local control and intelligent control.
Local Control: There is local control panel with several power steps; user can load/unload by button.
Intelligent Control: Through data processing software in PC, user can make automatic load, to display, record and manage the testing data, to form curves, tables, also to print them.