Hebei Kaixiang Electrical Technology Co., Ltd

Manufacturer from China
Active Member
7 Years
Home / Products / 3 Phase Load Bank /

2000 KW Full 3 Phase Load Bank , Dry Load Module Resistive Electrical Loads

Contact Now
Hebei Kaixiang Electrical Technology Co., Ltd
City:shijiazhuang
Province/State:hebei
Country/Region:china
Contact Now

2000 KW Full 3 Phase Load Bank , Dry Load Module Resistive Electrical Loads

Ask Latest Price
Video Channel
Brand Name :Kaixiang
Model Number :AC425V-2000kW
Certification :ISO9001
Place of Origin :China
MOQ :1 set
Price :negotiable
Payment Terms :L/C, T/T, Western Union
Supply Ability :80 Sets per Month
Delivery Time :Within 30 working days
Packaging Details :Container for Load bank
Power factor :0.8(lag)
Ambient Temperature :-10℃~+50℃
Rated Voltage :AC425V
Dimensions :About 4000mm×2350mm×2591mm(L×W×H)
Relative Humidity :≤95%
Frequency :50 HZ
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

AC425-2000kW 3 Phase Load Bank With Grey Colour And Good Performance

Product description

AC425-2000kW 3 Phase Load Bank is of independent research and development of electricity load test equipment by our technology, combining dry load module with the automatic measurement and control module, can accurately detect all kinds of generator output power and load capacity, full load and overload test.The system can be used with a computer to realize the intelligent control, automatically completing the special test to all electrical parameters of generating set and generating tables, graphs, and supporting the print, comprehensively from the cumbersome manual operation to provide scientific and efficient detection means for the power generating sets.

Technical Parameter

System Parameter
Rating voltage/frequency AC 3 phase 4 line, 425V/50Hz
Max Load Power Resistive Load: 2000kW
Load Resolution

Resistive Load: 18 steps,

1kW,2kW,2kW,5kW,10kW,10kW,20kW,50kW,100kW,200kW,200kW, 200kW,200kW,200kW,200kW,200kW,200kW,200kW

Power Factor 1
Load Tolerance (each step) ±5%
Load Tolerance (overall) ±3%
Fan &Control Voltage External AC 3 phase 4 line,415V/50Hz
Wire Connection

Load bank input——Copper bar (star coupling ”Y”)

Control power input——Connector-bar

Communication Interface RS485,RS232
Insulation F
Max Protection Grade IP54
Duty Cycle Continuous
Cooling Forced air cooling, by Axial Fan; horizontal inlet air, vertical exhaust cooling
Enclosure Container type,with a ladder, air inlet and outlet with mesh enclosure and protection door
Internal Lighting Adequate internal lighting will be provided
Transportation Hoisting, there are lifting lug in top of casing
Color Grey RAL7035 or as required
Dimensions About 4000mm×2350mm×2591mm(L×W×H)
Operating Environment Parameter
Ambient Temperature -10℃~+50℃
Relative Humidity ≤95%
Atmospheric Pressure 86~106kPa
Brands of Main Components
Contactor Schneider
Fuse Miro
PLC Siemens
Alloy Resistor (self-developing)
Data Processing Software (self-developing)
Main features

Overload protection with fan: when any fan cannot normally work, the load bank can unload automatically and give an alarm.

Emergency Stop: manually press the Emergency Stop switch on the panel, then load bank is in locked state, and cannot do any operation.

Protection Switch: some protection with switch, when misinformation or in special need, user can close the corresponding protection function temporarily.

Safety Monitor: through indicator lights on main interface, user can monitor system state. When system abnormally stop and protect, software interface prompt the cause immediately.

Short Circuit Protection and Over Current Protection: when short circuit, fuses in the load bank can insure to unload automatically.

Overheating Protection: temperature is over the safe threshold value, system unload automatically and give an alarm.

Smoke Fog Protection: If there is smoke fog in the container, system cut off load automatically and give an alarm.

Application

Large generator system testing in ocean engineering, drilling facilities,ship construction etc field
Factory testing for generator, static voltage characteristic test, speed characteristic test;
Marine generator overload protection test,parallel operation test,reverse power and reverse current protection test

2000 KW Full 3 Phase Load Bank , Dry Load Module Resistive Electrical Loads

Inquiry Cart 0