Ocean Engineering 440V 1500kVA Inductive Load Bank For Generator Testing
Product description
A resistive load bank, therefore, removes energy from the complete system: load bank from generator—generator from prime mover—prime mover from fuel. Additional energy is removed as a consequence of resistive load bank operation: waste heat from coolant, exhaust and generator losses and energy consumed by accessory devices. A resistive Load Bank impacts upon all aspects of a generating system.
Technical Parameter
RatingVoltage/Frequency |
angle form 440VAC/60Hz, Star class 400v 50hz |
Max Rated power |
Apparent Power: 1500kVA Resistive Power: 1200kW Reactive Power: 900kvar |
Load Resolution |
Resistive Load: 1.2.2.5.10.10.20.50.100.200.200.200.200.200kw Reactive load:1.2.2.5.10.10.20.50.100.200.200.200.200.200kvar |
PF(Power Factor) | 0.8 |
Load Tolerance (each step) | ±5% |
Load Tolerance(overall) | ±3% |
Display Precision | 0.5 class |
Control Power | 380VAC/50Hz, |
Wire Connection |
Load power supply input——Copper bar (star coupling) Control power supply input——Connector-bar |
Communication Interface | RS485, |
Casing Dimensions and Cooling | about 6058*2438*2896mm (length*width*height) Forced air cooling,Horizontal inlet air,Vertical cooling |
Weight | About 12000kgs/set |
Product Advantage
1. User can press the emergency stop button in the panel to unload immediately when the load bank is abnormal while working.
2. Over-load: Automatic load dump and give alarm when voltage is over safety thresholds.
3. Over-heat protection: Automatic load dump and give alarm when temperature is over safety thresholds.
4. Short Circuit Protection: Fuse could avoids damage to equipment when short circuit or current overload.
Application
KX Load Banks can be used to satisfy the requirements for emergency stand-by power systems. These requirements concern acceptance testing and periodic on-site testing and maintenance of emergency and stand-by power systems. The essence of the requirements is that emergency and stand-by power systems are to be tested under load.